 Current Transducer LA 03..20-PB
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 3 .. 20 A
Electrical data
Primary nominal r.m.s. current 1) IPN (A) 3 5 10 15 20 Primary current, measuring range IP (A) 4.5 7.5 15 22.5 30 Primary Current Limitation 3) (A) 3 3 5 7.5 10 Primary Conductor Diameter (mm) 0.5 0.5 0.65 0.8 1.0 Type
Features
* Closed loop (compensation) current
transducer using the Hall effect
LA LA LA LA LA
03-PB 05-PB 10-PB 15-PB 20-PB
* Voltage output * Printed circuit board mounting
VC IC R IS VOUT RL
Supply voltage ( 5 %) Current consumption app. Isolation resistance @ 500 VDC Output voltage @ IPN, RL = 10 k, TA = 25C Load resistance
15 V 20mA + IPN/1200mA > 500 M 4 V > 10 k
Advantages
* * * * * * *
Excellent accuracy Very good linearity Low temperature drift Optimized response time Wide frequency bandwidth No insertion losses High immunity to external interference * Current overload capacity
Accuracy-Dynamic performance data
X
L
VOE VOH VOT TC G tr f
Accuracy @ IPN, TA = 25C (without offset) Linearity error (0 .. IPN) Electrical offset voltage, TA = 25C Hysteresis offset voltage @ IP = 0; after an excursion of 1 x IPN Thermal drift of VOE (-10..+80C) (-20..-10C) Thermal drift of the gain (% of reading) (-10..+80C) (-20..-10C) Response time @ 90% of IP Frequency bandwidth (- 1dB)2)
< 1.5 < 1 < 30 < 15 < 1 < 2 < 0.04 < 0.08 <3 DC .. 150
% of IPN % of IPN mV mV mV/K mV/K %/K %/K s kHz
Applications
* AC variable speed drives and servo
motor drives
* Static converters for DC motor drives * Battery supplied applications * Uninterruptible Power Supplies
(UPS)
General data
TA TS m Ambient operating temperature Ambient storage temperature Mass - 20 .. + 80 - 30 .. + 85 < 12 C C g
* Switched Mode Power Supplies
(SMPS)
* Power supplies for welding
applications
Notes :
1)
2) 3)
Calibration for 4V output is carried out at the primary norminal r.m.s. current. Derating is needed to avoid excessive core heating at high frequency. Primary current is limited by primary wire size. Permanent primary current should not exceed the specified value.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
051102/6
Page 1/3
LEM Industrial
www.lem.com
Current transducer LA 03..20-PB Isolation characteristics
Vd dCp dCl CTI R.m.s. voltage for AC isolation test, 50 Hz, 1 mn Creepage distance Clearance distance Comparative Tracking Index (Group IIIa) 2.5 4) > 10 > 10 > 220 kV mm mm
Application examples
According to EN 50178 and CEI 61010-1 standards and following conditions :
* Over voltage category * Pollution degree PD2 * Non-uniform field
OV 3
EN 50178 dCp, dCl, Vw Single isolation Reinforced isolation Rated isolation voltage 1000 V 500 V
CEI 61010-1 Nominal voltage Cat III 1000 V rms Cat III 300 V rms
Notes :
4)
Between primary and secondary
051102/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. Page 2/3
LEM Industrial
www.lem.com
Dimensions LA 03..20-PB (in mm. 1 mm = 0.0394 inch)
Front V ie w
19 +/-1
Right V ie w
15 +/-1
20 +/-1
0.5
2
4321
Primary Conductor
See the attached table 6
4-0.5*0.25
6 +/-1
Bottom V ie w
5
11 +/-1
Signal Pins
4321 3-p=2.54
T erminal Pin Identification
Primary Conductor Part No. Diameter LA 03-PB 03-P 0.5 d LA 05-PB 05-P 0.5 d LA 10-PB 10-P 0.65 d LA 15-PB 15-P 0.8 d LA 20-PB 20-P 1.0 d Signal Pins 1 2 3 4 -Vcc 0V +Vcc Output
Direction of Current Flow
2.5 +/-1
5 (+)
6 +/-1
6 (-)
Safety
This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the following manufacturer's operating instructions.
Caution, risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected. 051102/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. Page 3/3
LEM Industrial
4.5 +/-1
www.lem.com


▲Up To Search▲   

 
Price & Availability of LA03-PB05

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X